品番: ACS880-01-293A-3
- 単位
- Chưa cập nhật
コンテンツを読み込み中…
オンライン決済は不要です。TESFA が品番、数量、供給条件を確認し、ご入力の連絡先へ見積を回答します。
MRO 品では、画像だけで選ぶより正しいコード確認が重要です。TESFA は見積確定前に主要な技術項目を確認します。

AF09-30-10-11 24-60V50/60HZ 20-60VDC Contactor. Mã ABB 1SBL137001R1110; ảnh và thông số từ trang sản phẩm chính hãng.
品番
1SBL137001R1110
単位
Chưa cập nhật
供給状況
Liên hệ báo giá
必要数量 (Chưa cập nhật)
オンライン決済は不要です。TESFA が品番、数量、供給条件を確認し、ご入力の連絡先へ見積を回答します。
MRO 品では、画像だけで選ぶより正しいコード確認が重要です。TESFA は見積確定前に主要な技術項目を確認します。
| 属性 | 製品仕様 |
|---|---|
| Mã đặt hàng | 1SBL137001R1110 |
| Extended Product Type | AF09-30-10-11 |
| Product ID | 1SBL137001R1110 |
| Catalog Description | AF09-30-10-11 24-60V50/60HZ 20-60VDC Contactor |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.27 kg |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1 |
| Rated Operational Voltage | Auxiliary Circuit 690 V; Main Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz; Control Circuit 50 / 60 Hz; Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A; acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 25 A; (690 V) 60 °C 25 A; (690 V) 70 °C 22 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 9 A; (440 V) 60 °C 9 A; (500 V) 60 °C 9.5 A; (690 V) 60 °C 7 A; (380 / 400 V) 60 °C 9 A; (220 / 230 / 240 V) 60 °C 9 A |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 9 A; (440 V) 60 °C 9 A; (500 V) 60 °C 9.5 A; (690 V) 60 °C 7 A; (380 / 400 V) 60 °C 9 A; (220 / 230 / 240 V) 60 °C 9 A |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A; (690 V) 2 A; (24 / 127 V) 6 A; (220 / 240 V) 4 A; (400 / 440 V) 3 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 10 A; (110 V) 1-Pole, 60 °C 10 A; (110 V) 1-Pole, 70 °C 10 A; (110 V) 2 Poles in Series, 40 °C 25 A; (110 V) 2 Poles in Series, 60 °C 25 A; (110 V) 2 Poles in Series, 70 °C 22 A; (110 V) 3 Poles in Series, 40 °C 25 A; (110 V) 3 Poles in Series, 60 °C 25 A; (110 V) 3 Poles in Series, 70 °C 22 A; (220 V) 2 Poles in Series, 40 °C 10 A; (220 V) 2 Poles in Series, 60 °C 10 A; (220 V) 2 Poles in Series, 70 °C 10 A; (220 V) 3 Poles in Series, 40 °C 25 A; (220 V) 3 Poles in Series, 60 °C 25 A; (220 V) 3 Poles in Series, 70 °C 22 A; (72 V) 1-Pole, 40 °C 25 A; (72 V) 1-Pole, 60 °C 25 A; (72 V) 1-Pole, 70 °C 22 A; (72 V) 2 Poles in Series, 40 °C 25 A; (72 V) 2 Poles in Series, 60 °C 25 A; (72 V) 2 Poles in Series, 70 °C 22 A; (72 V) 3 Poles in Series, 40 °C 25 A; (72 V) 3 Poles in Series, 60 °C 25 A; (72 V) 3 Poles in Series, 70 °C 22 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 6 A; (110 V) 1-Pole, 60 °C 6 A; (110 V) 1-Pole, 70 °C 6 A; (110 V) 2 Poles in Series, 40 °C 25 A; (110 V) 2 Poles in Series, 60 °C 25 A; (110 V) 2 Poles in Series, 70 °C 22 A; (110 V) 3 Poles in Series, 40 °C 25 A; (110 V) 3 Poles in Series, 60 °C 25 A; (110 V) 3 Poles in Series, 70 °C 22 A; (220 V) 2 Poles in Series, 40 °C 6 A; (220 V) 2 Poles in Series, 60 °C 6 A; (220 V) 2 Poles in Series, 70 °C 6 A; (220 V) 3 Poles in Series, 40 °C 25 A; (220 V) 3 Poles in Series, 60 °C 25 A; (220 V) 3 Poles in Series, 70 °C 22 A; (72 V) 1-Pole, 40 °C 25 A; (72 V) 1-Pole, 60 °C 25 A; (72 V) 1-Pole, 70 °C 22 A; (72 V) 2 Poles in Series, 40 °C 25 A; (72 V) 2 Poles in Series, 60 °C 25 A; (72 V) 2 Poles in Series, 70 °C 22 A; (72 V) 3 Poles in Series, 40 °C 25 A; (72 V) 3 Poles in Series, 60 °C 25 A; (72 V) 3 Poles in Series, 70 °C 22 A |
品番: ACS880-01-293A-3
品番: ACS880-01-032A-3
品番: ACS880-01-072A-3
品番: ACS880-01-045A-3
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.