Bộ nguồn SCHNEIDER ABLS1A24050. Range of product: Modicon Power Supply; Product or component type: Power supply.
品番
ABLS1A24050
単位
Bộ
供給状況
Liên hệ báo giá
必要数量 (Bộ)
オンライン決済は不要です。TESFA が品番、数量、供給条件を確認し、ご入力の連絡先へ見積を回答します。
MRO 品では、画像だけで選ぶより正しいコード確認が重要です。TESFA は見積確定前に主要な技術項目を確認します。
| 属性 | 製品仕様 |
|---|---|
| Mã sản phẩm | ABLS1A24050 |
| Range of product | Modicon Power Supply |
| Product or component type | Power supply |
| Power supply type | Regulated switch mode |
| Variant option | Optimized |
| Enclosure material | Aluminium |
| Nominal input voltage | 100...240 V AC single phase 100...240 V AC phase to phase 140...340 V DC |
| Rated power in W | 120 W |
| Output voltage | 24 V DC |
| Power supply output current | 5 A |
| Input voltage limits | 85...264 V AC without temperature derating 120...375 V DC without temperature derating |
| Nominal network frequency | 50…60 Hz |
| Network system compatibility | TN TT IT |
| Maximum leakage current | 1 mA 240 V AC |
| Input protection type | Integrated fuse (not interchangeable) 4 A External protection (recommended) 20 A Curve C External protection (recommended) 13 A Curve C |
| Inrush current | 30.0 A at 115 V 60.0 A at 230 V |
| Power factor | 0.55 at 115 V AC 0.45 at 230 V AC |
| Efficiency | 85 % at 115 V AC 88 % at 230 V AC |
| Output voltage adjustment | 22...28 V |
| Power dissipation in W | 25 W |
| Current consumption | < 1.3 A 140 V DC |
| Turn-on time | < 1 s |
| Holding time | > 20 ms 115 V AC > 40 ms 230 V AC |
| Startup with capacitive loads | 8000 µF |
| Residual ripple | < 120 mV |
| Meantime between failure [MTBF] | 700000 h at 25 °C, full load conforming to SR 332 |
| Output protection type | Against overload and short-circuits, protection technology: automatic reset Against over temperature, protection technology: manual reset Against overvoltage, protection technology: manual reset |
| Connections - terminals | Screw connection: 0.5...4 mm², (20 AWG...12 AWG) without wire end ferrule for output Screw connection: 0.5...2.5 mm², (20 AWG...14 AWG) with wire end ferrule for output Screw connection: 0.75...4 mm², (18 AWG...12 AWG) without wire end ferrule for input Screw connection: 0.75...4 mm², (18 AWG...12 AWG) with wire end ferrule for input |
| Line and load regulation | < 1 % at full voltage range in line at 25 °C |
| Status LED | 1 LED (green) output voltage |
| Depth | 117.6 mm |
| Height | 123.6 mm |
| Width | 40 mm |
| Net weight | 0.55 kg |
| Output coupling | Parallel Serial |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Double-profile DIN rail |
| Supply | SELV conforming to IEC 60950-1 SELV conforming to IEC 60204-1 SELV conforming to IEC 60364-4-41 |
| Dielectric strength | 3000 V AC with input to output |
| Service life | 10 year(s) |
| Overvoltage category | II |
| Standards | IEC 62368-1 EN/IEC 61204-3 IEC 61000-6-1 IEC 61000-6-2 IEC 61000-6-3 IEC 61000-6-4 IEC 61000-3-2 EN 61000-3-3 UL 62368-1 CSA C22.2 No 62368-1 UL 508 CSA C22.2 No 107.1 |
| Product certifications | CE CUL listed CUL recognized RCM CB Scheme EAC KC |
| Operating altitude | < 5000 m |
| Shock resistance | 150 m/s² for 11 ms |
| IP degree of protection | IP20 |
| Ambient air temperature for operation | -20…-10 °C with current derating of 2 % per °C mounting position A -10…40 °C without derating mounting position A 115 V AC -10…50 °C without derating mounting position A 230 V AC 40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC 50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m |
| Electrical shock protection class | Class I |
| Pollution degree | 2 |
| Vibration resistance | 3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6 10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic immunity | Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2 Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2 Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5 Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5 Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Immunity to voltage dips conforming to IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to IEC 61000-3-2 conforming to EN 55016-1-2 conforming to EN 55016-2-1 |
| Electromagnetic emission | Conducted emissions conforming to IEC 61000-6-3 Radiated emissions conforming to IEC 61000-6-4 |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 17.500 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 727.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 13 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
品番: XB5AA31
品番: XB5AA42
品番: LRD21
品番: XB5AD33
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.