物料编码: 3RA2816-0EW20
- 单位
- Chưa cập nhật
正在加载内容…
无需在线付款。TESFA 会核对物料代码、数量和供货条件,并根据您的联系方式回复报价。
对于 MRO 物料,确认正确型号比只看图片更重要。TESFA 会在确认报价前核对关键技术点。

Bộ điều khiển PLC SIEMENS 6ES7314-1AG14-0AB0. General information / Tên kiểu sản phẩm: CPU 314; General information / HW functional status: 01; General information / Firmware version: V3.3.
物料编码
6ES7314-1AG14-0AB0
单位
Chưa cập nhật
供货状态
Liên hệ báo giá
需求数量 (Chưa cập nhật)
无需在线付款。TESFA 会核对物料代码、数量和供货条件,并根据您的联系方式回复报价。
对于 MRO 物料,确认正确型号比只看图片更重要。TESFA 会在确认报价前核对关键技术点。
| 属性 | 产品规格 |
|---|---|
| Mã sản phẩm | 6ES7314-1AG14-0AB0 |
| Tên gọi chính hãng | ***spare part*** SIMATIC S7-300, CPU 314 central processing unit with MPI, integrated power supply 24 V DC, work memory 128 KB, Micro Memory Card required |
| General information / Tên kiểu sản phẩm | CPU 314 |
| General information / HW functional status | 01 |
| General information / Firmware version | V3.3 |
| General information / Engineering with / Programming package | STEP 7 V5.5 + SP1 or higher or STEP 7 V5.2 + SP1 or higher with HSP 218 |
| Supply voltage / Rated value (DC) | 24 V |
| Supply voltage / permissible range, lower limit (DC) | 19.2 V |
| Supply voltage / permissible range, upper limit (DC) | 28.8 V |
| Supply voltage / external protection for power supply lines (recommendation) | 2 A min. |
| Supply voltage / Mains buffering / Mains/voltage failure stored energy time | 5 ms |
| Supply voltage / Mains buffering / Repeat rate, min. | 1 s |
| Input current / Current consumption (rated value) | 650 mA |
| Input current / Current consumption (in no-load operation), typ. | 140 mA |
| Input current / Inrush current, typ. | 3.5 A |
| Input current / I²t | 1 A²·s |
| Power loss / Power loss, typ. | 4 W |
| Storage / Work memory / integrated | 128 kbyte |
| Storage / Work memory / expandable | No |
| Storage / Load memory / Plug-in (MMC) | Yes |
| Storage / Load memory / Plug-in (MMC), max. | 8 Mbyte |
| Storage / Load memory / Data management on MMC (after last programming), min. | 10 a |
| Storage / Backup / present | Yes; Guaranteed by MMC (maintenance-free) |
| Storage / Backup / without battery | Yes; Program and data |
| CPU processing times / for bit operations, typ. | 0.06 μs |
| CPU processing times / for word operations, typ. | 0.12 μs |
| CPU processing times / for fixed point arithmetic, typ. | 0.16 μs |
| CPU processing times / for floating point arithmetic, typ. | 0.59 μs |
| CPU-blocks / Number of elements (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
| CPU-blocks / DB / Number, max. | 1 024; Number range: 1 to 16000 |
| CPU-blocks / DB / Size, max. | 64 kbyte |
| CPU-blocks / FB / Number, max. | 1 024; Number range: 0 to 7999 |
| CPU-blocks / FB / Size, max. | 64 kbyte |
| CPU-blocks / FC / Number, max. | 1 024; Number range: 0 to 7999 |
| CPU-blocks / FC / Size, max. | 64 kbyte |
| CPU-blocks / OB / Number, max. | see instruction list |
| CPU-blocks / OB / Size, max. | 64 kbyte |
| CPU-blocks / OB / Number of free cycle OBs | 1; OB 1 |
| CPU-blocks / OB / Number of time alarm OBs | 1; OB 10 |
| CPU-blocks / OB / Number of delay alarm OBs | 2; OB 20, 21 |
| CPU-blocks / OB / Number of cyclic interrupt OBs | 4; OB 32, 33, 34, 35 |
| CPU-blocks / OB / Number of process alarm OBs | 1; OB 40 |
| CPU-blocks / OB / Number of startup OBs | 1; OB 100 |
| CPU-blocks / OB / Number of asynchronous error OBs | 4; OB 80, 82, 85, 87 |
| CPU-blocks / OB / Number of synchronous error OBs | 2; OB 121, 122 |
| CPU-blocks / Nesting depth / per priority class | 16 |
| CPU-blocks / Nesting depth / additional within an error OB | 4 |
| Counters, timers and their retentivity / S7 counter / Number | 256 |
| S7 counter / Retentivity / adjustable | Yes |
| S7 counter / Retentivity / preset | Z 0 to Z 7 |
| S7 counter / Counting range / lower limit | 0 |
| S7 counter / Counting range / upper limit | 999 |
| Counters, timers and their retentivity / IEC counter / present | Yes |
| Counters, timers and their retentivity / IEC counter / Type | SFB |
| Counters, timers and their retentivity / IEC counter / Number | Unlimited (limited only by RAM capacity) |
| Counters, timers and their retentivity / S7 timer / Number | 256 |
| S7 timer / Retentivity / adjustable | Yes |
| S7 timer / Retentivity / preset | No retentivity |
| S7 timer / Time range / lower limit | 10 ms |
| S7 timer / Time range / upper limit | 9 990 s |
| Counters, timers and their retentivity / IEC timer / present | Yes |
| Counters, timers and their retentivity / IEC timer / Type | SFB |
| Counters, timers and their retentivity / IEC timer / Number | Unlimited (limited only by RAM capacity) |
| Data areas and their retentivity / Retentive data area (incl. timers, counters, flags), max. | 64 kbyte |
| Data areas and their retentivity / Flag / Size, max. | 256 byte |
| Data areas and their retentivity / Flag / Retentivity available | Yes; MB 0 to MB 255 |
| Data areas and their retentivity / Flag / Retentivity preset | MB 0 to MB 15 |
| Data areas and their retentivity / Flag / Number of clock memories | 8; 1 memory byte |
| Retentivity adjustable | Yes; via non-retain property on DB |
| Retentivity preset | Yes |
| Local data / per priority class, max. | 32 kbyte; Max. 2 KB per block |
| Address area / I/O address area / Inputs | 1 024 byte |
| Address area / I/O address area / Outputs | 1 024 byte |
| Address area / Process image / Inputs | 1 024 byte |
| Address area / Process image / Outputs | 1 024 byte |
| Address area / Process image / Inputs, adjustable | 1 024 byte |
| Address area / Process image / Outputs, adjustable | 1 024 byte |
| Address area / Process image / Inputs, default | 128 byte |
| Address area / Process image / Outputs, default | 128 byte |
| Address area / Digital channels / Inputs | 1 024 |
| Address area / Digital channels / of which central | 1 024 |
| Address area / Digital channels / Outputs | 1 024 |
| Address area / Analog channels / Inputs | 256 |
| Address area / Analog channels / of which central | 256 |
| Address area / Analog channels / Outputs | 256 |
| Hardware configuration / Number of expansion units, max. | 3 |
| Hardware configuration / Number of DP masters / integrated | 0 |
| Hardware configuration / Number of DP masters / via CP | 4 |
| Hardware configuration / Number of operable FMs and CPs (recommended) / FM | 8 |
| Hardware configuration / Number of operable FMs and CPs (recommended) / CP, PtP | 8 |
| Hardware configuration / Number of operable FMs and CPs (recommended) / CP, LAN | 10 |
| Hardware configuration / Rack / Racks, max. | 4 |
| Hardware configuration / Rack / Modules per rack, max. | 8 |
| Time of day / Clock / Hardware clock (real-time) | Yes |
| Time of day / Clock / retentive and synchronizable | Yes |
| Time of day / Clock / Backup time | 6 wk; At 40 °C ambient temperature |
| Time of day / Clock / Deviation per day, max. | 10 s; Typ.: 2 s |
| Time of day / Clock / Behavior of the clock following POWER-ON | Clock continues running after POWER OFF |
| Time of day / Clock / Behavior of the clock following expiry of backup period | the clock continues at the time of day it had when power was switched off |
| Time of day / Operating hours counter / Number | 1 |
| Time of day / Operating hours counter / Number/Number range | 0 |
| Time of day / Operating hours counter / Range of values | 0 to 2^31 hours (when using SFC 101) |
物料编码: 3RA2816-0EW20
物料编码: 3RT2035-1NB30
物料编码: 6MF2805-0AA00
物料编码: 6ES7440-1CS00-0YE0
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.