物料编码: IFS203
- 单位
- Chưa cập nhật
正在加载内容…
无需在线付款。TESFA 会核对物料代码、数量和供货条件,并根据您的联系方式回复报价。
对于 MRO 物料,确认正确型号比只看图片更重要。TESFA 会在确认报价前核对关键技术点。

Cảm biến lưu lượng IFM SM0510. Number of inputs and outputs: Number of digital outputs: 2; Number of analog outputs: 1; Measuring range: 5...900 l/min: 0.3...54 m³/h.
物料编码
SM0510
单位
Chưa cập nhật
供货状态
联系报价
需求数量 (Chưa cập nhật)
无需在线付款。TESFA 会核对物料代码、数量和供货条件,并根据您的联系方式回复报价。
对于 MRO 物料,确认正确型号比只看图片更重要。TESFA 会在确认报价前核对关键技术点。
| 属性 | 产品规格 |
|---|---|
| Mã sản phẩm | SM0510 |
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range | 5...900 l/min: 0.3...54 m³/h |
| Process connection | threaded connection G 2 external thread DN50 flat seal |
| Special feature | gold-plated contacts |
| Application | Totalizer function; empty pipe detection; for industrial applications |
| Installation | connection to pipe by means of an adapter |
| Media | Conductive liquids; water; water-based media |
| Note on media | conductivity: ≥ 20 µS/cm; viscosity: < 70 mm²/s (40 °C) |
| Medium temperature [°C] | -10...90 |
| Pressure rating | 16 bar: 1.6 MPa |
| MAWP (for applications according to CRN) | 8.9 bar: 0.89 MPa |
| Operating voltage [V] | 18...32 DC; (to SELV/PELV) |
| Current consumption [mA] | < 150 |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 5 |
| Measuring principle | magnetic-inductive |
| Inputs | counter reset |
| Total number of outputs | 2 |
| Output signal | switching signal; analog signal; pulse signal; frequency signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / closed; (configurable) |
| Max. voltage drop switching output DC [V] | 2 |
| Permanent current rating of switching output DC [mA] | 250; (per output) |
| Number of analog outputs | 1 |
| Analog current output [mA] | 4...20; (scalable) |
| Max. load [Ω] | 500 |
| Analog voltage output [V] | 0...10; (scalable) |
| Min. load resistance [Ω] | 2000 |
| Pulse output | flow rate meter |
| Short-circuit protection | yes |
| Type of short-circuit protection | yes (non-latching) |
| Overload protection | yes |
| Frequency of the output [Hz] | 0.1...10000 |
| Display range | -920...920 l/min: -55.2...55.2 m³/h |
| Resolution | 1 l/min: 0.05 m³/h |
| Set point SP | 10...900 l/min: 0.55...54 m³/h |
| Reset point rP | 5...896 l/min: 0.3...53.75 m³/h |
| Analog start point ASP | 0...720 l/min: 0...43.2 m³/h |
| Analog end point AEP | 180...900 l/min: 10.8...54 m³/h |
| Low flow cut-off LFC | < 15 l/min: < 0.9 m³/h |
| In steps of | 1 l/min: 0.05 m³/h; 0.1 l |
| Measuring dynamics | 1:180 |
| Pulse value | 0.1 l...600 x 10³ m³ |
| Pulse length [s] | 0,003...2 |
| Measuring range [°C] | -20...80 |
| Display range [°C] | -40...100 |
| Resolution [°C] | 0.2 |
| Set point SP [°C] | -19.2...80 |
| Reset point rP [°C] | -19.6...79.6 |
| Analog start point [°C] | -20...60 |
| Analog end point [°C] | 0...80 |
| In steps of [°C] | 0.2 |
| Accuracy (in the measuring range) | ± (0,8 % MW + 0,5 % MEW) |
| Repeatability | ± 0,2% MEW |
| Temperature drift | ± 0,0333 °C / K |
| Accuracy [K] | ± 1 (bei 25 °C, Q > 15 l/min) |
| Response time [s] | 0.35; (dAP = 0) |
| Delay time programmable dS, dr [s] | 0...50 |
| Damping process value dAP [s] | 0...5 |
| Dynamic response T05 / T09 [s] | T09 = 3 (Q > 15 l/min) |
| Parameter setting options | Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / closed; switching logic; current/voltage/frequency/pulse output; Start-up delay; display can be deactivated; Display unit; empty pipe detection |
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 CDV |
| Profiles | Smart Sensor - SSP 0: Generic Profiled Sensor; Function: Device identification; Function: Process data variable |
| SIO mode | yes |
| Required master port class | A |
| Process data analog | 3 |
| Process data binary | 2 |
| Min. process cycle time [ms] | 5 |
| Supported DeviceIDs | Type of operation: DeviceID; default: 509 |
| Ambient temperature [°C] | -10...60 |
| Storage temperature [°C] | -25...80 |
| Protection | IP 65; IP 67 |
| EMC | DIN EN 61000-4-2 ESD: 4 kV CD / 8 kV AD; DIN EN 61000-4-3 HF radiated: 10 V/m; DIN EN 61000-4-4 Burst: 2 kV; DIN EN 61000-4-5 Surge: 1 kV; DIN EN 61000-4-6 HF conducted: 10 V |
| CPA approval | model number: 004MI; accuracy class: -; maximum allowable error: ± 1,5 % FS; Q (min): 0,3 m³/h; Q (t): -; Q (max): 54 m³/h; Medium temperature: -10...70 °C |
| Shock resistance | DIN EN 60068-2-27: 20 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6: 5 g (10...2000 Hz) |
| MTTF [years] | 85 |
| UL approval | UL approval number: I008; File number UL: E174189 |
| Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight [g] | 3212 |
| Housing | rectangular |
| Inlet pipe length | 3 x DN |
| Outlet pipe length | 1 x DN |
| Dimensions [mm] | 200 x 103 x 117 |
| Material | stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PC; FKM; PBT-GF20; TPE-U |
| Materials (wetted parts) | Pipe section: stainless steel (1.4404 / 316L); Process connection sealing: NBR fiber-reinforced Gasket; FKM; stainless steel (1.4571/316Ti ); PEEK |
| Display | Display unit: 6 x LED, green (l/min, m³/h, l, m³, 10³, °C); Switching status: 2 x LED, yellow; Measured values: alphanumeric display, 4-digit; Programming: alphanumeric display, 4-digit |
| Items supplied | sealings: 2, Centellen; Label |
| Remarks | MW = Measured value; MEW = Final value of the measuring range |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |
物料编码: IFS203
物料编码: EVT406
物料编码: IG5526
物料编码: II5961
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.