Item code: 3RA2816-0EW20
- Unit
- Chưa cập nhật
Loading content…
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.

Aptomat SIEMENS 3VA1150-4EE32-0AA0. Model / product brand name: SENTRON; Model / product designation: Molded case circuit breaker; Model / design of the product: Line protection.
Item code
3VA1150-4EE32-0AA0
Unit
Cái
Supply status
Liên hệ báo giá
Required quantity (Cái)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | 3VA1150-4EE32-0AA0 |
| Tên gọi chính hãng | circuit breaker 3VA1 IEC Frame 160 breaking capacity class S Icu=36 kA @ 415 V 3-pole, line protection TM220, ATFM, In=50 A overload protection Ir=35 A...50 A short-circuit protection Ii=10 x In nut keeper kit |
| Model / product brand name | SENTRON |
| Model / product designation | Molded case circuit breaker |
| Model / design of the product | Line protection |
| Model / design of the overcurrent release | TM220 |
| Model / protection function of the overcurrent release | LI |
| Model / number of poles | 3 |
| General technical data / insulation voltage / rated value | 800 V |
| General technical data / operating voltage / at DC / rated value | 500 V |
| General technical data / operating voltage / at AC / rated value | 690 V |
| General technical data / power loss [W] / maximum | 14.6 W |
| General technical data / power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 4.87 W |
| General technical data / mechanical service life (operating cycles) / typical | 20 000 |
| General technical data / electrical endurance (operating cycles) / at AC-1 / at 380/415 V | 9 000 |
| General technical data / electrical endurance (operating cycles) / at AC-1 / at 690 V | 6 300 |
| General technical data / product feature / for neutral conductors / upgradable/retrofittable / short-circuit and overload proof | No |
| General technical data / ground-fault monitoring version | Without |
| General technical data / product function / communication function | No |
| General technical data / product function / other measurement function | No |
| General technical data / Net Weight | 921 g |
| Current / operational current / at 40 °C | 50 A |
| Current / operational current / at 45 °C | 50 A |
| Current / operational current / at 50 °C | 50 A |
| Current / operational current / at 55 °C | 49 A |
| Current / operational current / at 60 °C | 48 A |
| Current / operational current / at 65 °C | 46 A |
| Current / operational current / at 70 °C | 45 A |
| Switching capacity according to IEC 60947 / switching capacity class of the circuit breaker | S |
| at 240 V | 55 kA |
| at 415 V | 36 kA |
| at 440 V | 25 kA |
| at 500 V | 7 kA |
| at 690 V | 7 kA |
| operating short-circuit current breaking capacity (Ics) / at 240 V | 55 kA |
| operating short-circuit current breaking capacity (Ics) / at 415 V | 36 kA |
| operating short-circuit current breaking capacity (Ics) / at 440 V | 25 kA |
| operating short-circuit current breaking capacity (Ics) / at 500 V | 5 kA |
| operating short-circuit current breaking capacity (Ics) / at 690 V | 5 kA |
| short-circuit current making capacity (Icm) / at 240 V | 121 kA |
| short-circuit current making capacity (Icm) / at 415 V | 75.6 kA |
| short-circuit current making capacity (Icm) / at 440 V | 52.5 kA |
| short-circuit current making capacity (Icm) / at 500 V | 11.9 kA |
| short-circuit current making capacity (Icm) / at 690 V | 11.9 kA |
| design of short-circuit protection | For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter |
| Adjustable parameters / product feature / for L-tripping / can be switched on/off | No |
| Adjustable parameters / I2t characteristic / minimum | 35 A |
| Adjustable parameters / I2t characteristic / maximum | 50 A |
| Adjustable parameters / characteristic / minimum | 1 s |
| Adjustable parameters / characteristic / maximum | 1 s |
| Adjustable parameters / adjustable response value setting current (Ii) / for I-tripping / minimum | 500 A |
| Adjustable parameters / adjustable response value setting current (Ii) / for I-tripping / maximum | 500 A |
| Adjustable parameters / adjustable setting current (InN) / for N-tripping / minimum | 0 A |
| Adjustable parameters / adjustable setting current (InN) / for N-tripping / maximum | 0 A |
| Adjustable parameters / product function / grounding protection | No |
| Mechanical Design / product component / undervoltage release | No |
| Mechanical Design / product component / voltage trigger | No |
| Mechanical Design / product component / trip indicator | No |
| Mechanical Design / height [in] | 5.12 in |
| Mechanical Design / height | 130 mm |
| Mechanical Design / width [in] | 3 in |
| Mechanical Design / width | 76.2 mm |
| Mechanical Design / depth [in] | 2.76 in |
| Mechanical Design / depth | 70 mm |
| Connections / arrangement of electrical connectors / for main current circuit | Front terminal |
| Connections / type of electrical connection / for main current circuit | nut keeper kit on both ends |
| Connections / type of connectable conductor cross-sections / for flat-bar terminal connection / minimum | 12 x 1 mm |
| Connections / type of connectable conductor cross-sections / for flat-bar terminal connection / maximum | 17 x 6,5 mm |
| Connections / design of the surface / of the connections / on the top of the switch (N, 1, 3, 5) | Silver |
| Connections / design of the surface / of the connections / on the bottom of the switch (N, 2, 4, 6) | Tin |
| Auxiliary circuit / number of CO contacts / for auxiliary contacts | 0 |
| Accessories / product extension / optional / motor drive | Yes |
| Environmental conditions / protection class IP / on the front | IP40 |
| Environmental conditions / ambient temperature / during operation / minimum | -25 °C |
| Environmental conditions / ambient temperature / during operation / maximum | 70 °C |
| Environmental conditions / ambient temperature / during storage / minimum | -40 °C |
| Environmental conditions / ambient temperature / during storage / maximum | 80 °C |
| Environmental footprint / Environmental Product Declaration(EPD) | Yes |
| Environmental footprint / global warming potential [CO2 eq] / total | 190 kg |
| Environmental footprint / global warming potential [CO2 eq] / during manufacturing | 4.67 kg |
| Environmental footprint / global warming potential [CO2 eq] / during operation | 186 kg |
| Environmental footprint / global warming potential [CO2 eq] / after end of life | -0.826 kg |
| Environmental footprint / reference code / according to IEC 81346-2 | Q |
Item code: 3RA2816-0EW20
Item code: 3RT2035-1NB30
Item code: 6MF2805-0AA00
Item code: 6ES7440-1CS00-0YE0
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.