Module ngõ ra số SIEMENS 6ES7132-6BD21-0BA0. General information / Tên kiểu sản phẩm: DQ 4x24VDC/2A ST; General information / HW functional status: 01; General information / Firmware version: V1.0.
Item code
6ES7132-6BD21-0BA0
Unit
Cái
Supply status
Liên hệ báo giá
Required quantity (Cái)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | 6ES7132-6BD21-0BA0 |
| Tên gọi chính hãng | SIMATIC ET 200SP, digital output module DQ 4x24 V DC/2 A standard, source output (PNP,sourcing output) packing unit: 1 unit, suitable for BU type A0, color code CC02, substitute value output, module diagnostics for: short circuit to L+ and M, wire break, supply voltage |
| General information / Tên kiểu sản phẩm | DQ 4x24VDC/2A ST |
| General information / HW functional status | 01 |
| General information / Firmware version | V1.0 |
| General information / FW update possible | Yes |
| General information / usable BaseUnits | BU type A0 |
| General information / Color code for module-specific color-coded label | CC02 |
| General information / Product function / I&M data | Yes; I&M0 to I&M3 |
| General information / Product function / Isochronous mode | No |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | STEP 7 V19 or higher with HSP0425 / integrated as of TIA Portal V20 |
| General information / Engineering with / STEP 7 configurable/integrated from version | as of STEP 7 V5.5 SP3 with HSP0230 V11.0 / integrated as of STEP 7 V5.7 SP3 |
| General information / Engineering with / PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| General information / Engineering with / PROFINET from GSD version/GSD revision | GSDML V2.43 |
| General information / Operating mode / DQ | Yes |
| General information / Operating mode / DQ with energy-saving function | No |
| General information / Operating mode / PWM | No |
| General information / Operating mode / Oversampling | No |
| General information / Operating mode / MSO | No |
| Supply voltage / Rated value (DC) | 24 V |
| Supply voltage / permissible range, lower limit (DC) | 19.2 V |
| Supply voltage / permissible range, upper limit (DC) | 28.8 V |
| Supply voltage / Reverse polarity protection | Yes |
| Input current / Current consumption, max. | 20 mA; without load |
| Output voltage / Rated value (DC) | 24 V |
| Power loss / Power loss, typ. | 1 W |
| Address area / Address space per module / Address space per module, max. | 1 byte; + 1 byte for QI information |
| Hardware configuration / Automatic encoding | Yes |
| Hardware configuration / Mechanical coding element | Yes |
| Hardware configuration / Type of mechanical coding element | Type A |
| Hardware configuration / Selection of BaseUnit for connection variants / 1-wire connection | BU type A0 |
| Hardware configuration / Selection of BaseUnit for connection variants / 2-wire connection | BU type A0 |
| Hardware configuration / Selection of BaseUnit for connection variants / 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| Digital outputs / Type of digital output | Source output (PNP, current-sourcing) |
| Digital outputs / Số ngõ ra số | 4 |
| Digital outputs / Current-sinking | No |
| Digital outputs / Current-sourcing | Yes |
| Digital outputs / Digital outputs, parameterizable | Yes |
| Digital outputs / output type acc. to IEC 61131, type 2 | Yes |
| Digital outputs / Short-circuit protection | Yes; Electronic |
| Digital outputs / Response threshold, typ. | 2.8 to 5.2 A |
| Digital outputs / Open-circuit detection | Yes |
| Digital outputs / Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
| Digital outputs / Controlling a digital input | Yes; supports input type 3 according to IEC 61131-2 |
| Digital outputs / Switching capacity of the outputs / with resistive load, max. | 2 A |
| Digital outputs / Switching capacity of the outputs / with inductive load, max. | 2 A |
| Digital outputs / Switching capacity of the outputs / on lamp load, max. | 10 W |
| Digital outputs / Load resistance range / lower limit | 12 Ω |
| Digital outputs / Load resistance range / upper limit | 3 400 Ω |
| Digital outputs / Output current / for signal "1" rated value | 2 A |
| Digital outputs / Output current / for signal "1" permissible range, max. | 2 A |
| Digital outputs / Output current / for signal "0" residual current, max. | 0.1 mA |
| Digital outputs / Output delay with resistive load / "0" to "1", typ. | 50 μs |
| Digital outputs / Output delay with resistive load / "1" to "0", typ. | 100 μs |
| Digital outputs / Parallel switching of two outputs / for uprating | No |
| Digital outputs / Parallel switching of two outputs / for redundant control of a load | Yes |
| Digital outputs / Switching frequency / with resistive load, max. | 100 Hz |
| Digital outputs / Switching frequency / with inductive load, max. | 0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads" |
| Digital outputs / Switching frequency / on lamp load, max. | 10 Hz |
| Digital outputs / Total current of the outputs / Current per channel, max. | 2 A |
| Digital outputs / Total current of the outputs / Current per module, max. | 8 A; see Equipment Manual "Derating curve" |
| Total current of the outputs (per module) / horizontal installation / up to 30 °C, max. | 8 A |
| Total current of the outputs (per module) / horizontal installation / up to 40 °C, max. | 8 A |
| Total current of the outputs (per module) / horizontal installation / up to 50 °C, max. | 6 A |
| Total current of the outputs (per module) / horizontal installation / up to 60 °C, max. | 4 A |
| Total current of the outputs (per module) / vertical installation / up to 30 °C, max. | 8 A |
| Total current of the outputs (per module) / vertical installation / up to 40 °C, max. | 6 A |
| Total current of the outputs (per module) / vertical installation / up to 50 °C, max. | 4 A |
| Digital outputs / Cable length / shielded, max. | 1 000 m |
| Digital outputs / Cable length / unshielded, max. | 600 m |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Alarms / Diagnostic alarm | Yes |
| Diagnoses / Monitoring the supply voltage | Yes |
| Diagnoses / parameterizable | Yes |
| Diagnoses / Wire break | Yes; module-wise |
| Diagnoses / Short-circuit to ground | Yes; module-wise |
| Diagnoses / Short-circuit to L+ | Yes; module-wise |
| Diagnoses / Group error | Yes |
| Diagnostics indication LED / Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED / Channel status display | Yes; green LED |
| Diagnostics indication LED / for channel diagnostics | No |
| Diagnostics indication LED / for module diagnostics | Yes; green/red DIAG LED |
| Potential separation / Potential separation channels / between the channels | No |
| Potential separation / Potential separation channels / between the channels and backplane bus | Yes |
| Potential separation / Potential separation channels / Between the channels and load voltage L+ | No |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Ambient conditions / Ambient temperature during operation / horizontal installation, min. | -30 °C |
| Ambient conditions / Ambient temperature during operation / horizontal installation, max. | 60 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, min. | -30 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, max. | 50 °C |
| Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual |
| Dimensions / Chiều rộng | 15 mm |
| Dimensions / Chiều cao | 73 mm |
| Dimensions / Chiều sâu | 58 mm |
| Weights / Khối lượng xấp xỉ | 30 g |
Item code: 3RA2816-0EW20
Item code: 3RT2035-1NB30
Item code: 6MF2805-0AA00
Item code: 6ES7440-1CS00-0YE0
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.