Item code: IFS203
- Unit
- Chưa cập nhật
Loading content…
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.

Cảm biến áp suất IFM PG2797. Number of inputs and outputs: Number of digital outputs: 1; Number of analog outputs: 1; Measuring range: -0.05...1 bar: -50...1000 mbar: -0.73...14.5 psi.
Item code
PG2797
Unit
Chưa cập nhật
Supply status
Contact for quote
Required quantity (Chưa cập nhật)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | PG2797 |
| Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 |
| Measuring range | -0.05...1 bar: -50...1000 mbar: -0.73...14.5 psi |
| Process connection | threaded connection G 1 external thread with Aseptoflex Vario sealing contour |
| Note | G1 Gewinde nach ISO 228. Alternativ dichtend über rückwärtige Dichtkontur mit Dichtung in Anlehnung an DIN EN ISO 1179-2. |
| Special feature | gold-plated contacts |
| Application | flush mountable for the food and beverage industry |
| Media | viscous media and liquids with suspended particles; liquids and gases |
| Medium temperature [°C] | -25...125; (145 max. 1h) |
| Min. burst pressure | 30 bar: 435 psi: 3 MPa |
| Pressure rating | 10 bar: 145 psi: 1 MPa |
| Type of pressure | relative pressure |
| No dead space | yes |
| MAWP (for applications according to CRN) [bar] | 10 |
| Operating voltage [V] | 18...32 DC |
| Current consumption [mA] | < 70; (24 V) |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 6 |
| Integrated watchdog | yes |
| Total number of outputs | 2 |
| Output signal | switching signal; analog signal; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 1 |
| Output function | normally open / closed; (configurable) |
| Max. voltage drop switching output DC [V] | 2 |
| Permanent current rating of switching output DC [mA] | 250 |
| Switching frequency DC [Hz] | 50 |
| Number of analog outputs | 1 |
| Analog current output [mA] | 4...20, invertible; (scalable) |
| Max. load [Ω] | (Ub - 10 V) / 20 mA |
| Short-circuit protection | yes |
| Type of short-circuit protection | yes (non-latching) |
| Overload protection | yes |
| Set point SP | -0.048...1.6 bar: -0.7...23.21 psi |
| Reset point rP | -0.05...1.598 bar: -0.73...23.18 psi |
| Analog start point | -0.05...1.35 bar: -0.73...19.58 psi |
| Analog end point | 0.2...1.6 bar: 2.9...23.21 psi |
| In steps of | 0.001 bar: 0.01 psi |
| Switch point accuracy [% of the span] | < ± 0,5; (Turn down 1:1) |
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation [% of the span] | < ± 0,5; (Turn down 1:1 , linearity, incl. hysteresis and repeatability , limit value setting to DIN EN IEC 62828-1) |
| Linearity deviation [% of the span] | < ± 0,15; (Turn down 1:1) |
| Hysteresis deviation [% of the span] | < ± 0,15; (Turn down 1:1) |
| Long-term stability [% of the span] | < ± 0,1; (Turn down 1:1; per year) |
| Temperature coefficient zero point [% of the span / 10 K] | < ± 0,05; (0...70 °C) |
| Temperature coefficient span [% of the span / 10 K] | < ± 0,15; (0...70 °C) |
| Response time [ms] | < 10 |
| Damping process value dAP [s] | 0.01...30 |
| Damping for the analog output dAA [s] | 0.01...30 |
| Step response time analog output [ms] | 25 |
| Ambient temperature [°C] | -25...80 |
| Storage temperature [°C] | -40...100 |
| Protection | IP 67; IP 69K |
| EMC | EN 61000-4-2 ESD: 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated: 10 V/m; EN 61000-4-4 Burst: 2 kV; EN 61000-4-5 Surge: 0,5/1 kV; EN 61000-4-6 HF conducted: 10 V |
| Shock resistance | DIN EN 60068-2-27: 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6: 10 g (10...2000 Hz) |
| MTTF [years] | 100 |
| Note on approval | Factory certificate available as download at www.factory-certificate.ifm |
| Weight [g] | 521.2 |
| Dimensions [mm] | 153 x 100 x 57 |
| Material | stainless steel (1.4404 / 316L); PA; FKM; PTFE; viewing glass: laminated safety glass 4 mm |
| Materials (wetted parts) | stainless steel (1.4435 / 316L) surface characteristics: Ra < 0,4 µm / Rz = 4 µm; ceramics (99.9 % Al2O3); PTFE |
| Min. pressure cycles | 100 million |
| Display | Display unit: 2 x LED, green; Switching status: LED, yellow; Switch points: LED ring, red; Function display: alphanumeric display, red 4-digit; Measured values: analog display, 0...350° rotatable, pointer not visible when unit disconnected; Measured values: alphanumeric display, red 4-digit |
| With scale | yes |
| Extended display range (max.) | 1.6 bar: 23.21 psi |
| Remarks | characteristics deviation in the extended display range:1.5 % of the span; switch point accuracy in the extended display range: 1.5 % of the span |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |
Item code: IFS203
Item code: EVT406
Item code: IG5526
Item code: II5961
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.