Item code: 060-110191
- Unit
- Cái
Loading content…
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.

Cảm biến áp suất IFM PN7094. Number of inputs and outputs: Number of digital outputs: 2; Measuring range: -1...10 bar: -14.5...145 psi: -0.1...1 MPa.
Item code
PN7094
Unit
Cái
Supply status
Liên hệ báo giá
Required quantity (Cái)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | PN7094 |
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | -1...10 bar: -14.5...145 psi: -0.1...1 MPa |
| Process connection | threaded connection G 1/4 Internal thread |
| Special feature | gold-plated contacts |
| Measuring element | ceramic-capacitive pressure measuring cell |
| Application | for industrial applications |
| Media | liquids and gases |
| Medium temperature [°C] | -25...80 |
| Min. burst pressure | 150 bar: 2175 psi: 15 MPa |
| Pressure rating | 75 bar: 1087 psi: 7.5 MPa |
| Vacuum resistance | -1000 mbar: -0.1 MPa |
| Type of pressure | relative pressure; vacuum |
| Operating voltage [V] | 18...30 DC; (to SELV/PELV) |
| Current consumption [mA] | < 35 |
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | < 0.3 |
| Integrated watchdog | yes |
| Total number of outputs | 2 |
| Output signal | switching signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / closed; (configurable) |
| Max. voltage drop switching output DC [V] | 2.5 |
| Permanent current rating of switching output DC [mA] | 150; (200 (...60 °C) 250 (...40 °C)) |
| Switching frequency DC [Hz] | < 170 |
| Short-circuit protection | yes |
| Type of short-circuit protection | yes (non-latching) |
| Overload protection | yes |
| Set point SP | -0.9...10 bar: -13.5...145 psi: -0.09...1 MPa; -0.92...10 bar: -13.3...145 psi: -0.092...1 MPa |
| Reset point rP | -0.95...9.95 bar: -14...144.5 psi: -0.095...0.995 MPa; -0.97...9.95 bar: -14...144.3 psi: -0.097...0.995 MPa |
| Min. difference between SP and rP | 0.05 bar: 1 psi: 0.005 MPa; 0.05 bar: 0.8 psi: 0.005 MPa |
| In steps of | 0.05 bar: 0.5 psi: 0.005 MPa; 0.01 bar: 0.1 psi: 0.001 MPa |
| Switch point accuracy [% of the span] | < ± 0,5 |
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span] | < ± 0,25 |
| Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (0...80 °C) |
| Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (0...80 °C) |
| Response time [ms] | < 3 |
| Delay time programmable dS, dr [s] | 0...50 |
| Parameter setting options | hysteresis / window; normally open / closed; switching logic; switch-on/switch-off delay; Damping; Display unit |
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| SIO mode | yes |
| Required master port class | A; (when pin 2 not connected: B) |
| Supported DeviceIDs | Type of operation: DeviceID; Factory setting / CMPT = 2: 403; Status_B High Resolution / CMPT = 3: 601 |
| Note | For further information please see the IODD PDF file at "Downloads" |
| Profiles | Smart Sensor - SSP 0: Generic Profiled Sensor; Function: Device identification; Function: Process data variable; Function: Device diagnosis; Smart Sensor - SSP 3.1: Measuring Sensor; Common - I&D: Identification and Diagnosis |
| Min. process cycle time [ms] | 2.3; 3 |
| IO-Link resolution pressure | 0.01 bar: 0.001 MPa; 0.005 bar: 0.0005 MPa |
| IO-Link process data (cyclical) | Function: bit length; pressure: 14; binary switching information: 2; Function: bit length; pressure: 16; device status: 4; binary switching information: 2 |
| IO-Link functions (acyclical) | application specific tag |
| Ambient temperature [°C] | -25...80 |
| Storage temperature [°C] | -40...100 |
| Protection | IP 65; IP 67 |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN EN 60068-2-27: 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6: 20 g (10...2000 Hz) |
| MTTF [years] | 260 |
| UL approval | UL approval number: J001 |
| Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight [g] | 241.7 |
| Housing | tubular |
| Dimensions [mm] | Ø 34 / L = 90.7 |
| Material | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Materials (wetted parts) | stainless steel (1.4404 / 316L); ceramics; FKM |
| Min. pressure cycles | 100 million |
| Tightening torque [Nm] | 25...35; (recommended tightening torque; Depends on lubrication, seal and pressure rating) |
| Display | Display unit: 3 x LED, green (bar, psi, MPa); Switching status: 2 x LED, yellow; Measured values: alphanumeric display, red/green 4-digit |
| Pack quantity | 1 pcs. |
| Connector | 1 x M12; coding: A; Contacts: 4, gold-plated |
Item code: 060-110191
Item code: 060-117191
Item code: IFS203
Item code: EVT406
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.