Module ngõ ra số SIEMENS 6ES7136-6DB01-0CA0. General information / Tên kiểu sản phẩm: F-DQ 4x 24 V DC/2 A PM HF; General information / Firmware version / FW update possible: Yes; General information / usable BaseUnits: BU type A0.
Item code
6ES7136-6DB01-0CA0
Unit
Chưa cập nhật
Supply status
Contact for quote
Required quantity (Chưa cập nhật)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | 6ES7136-6DB01-0CA0 |
| Tên gọi chính hãng | SIMATIC DP, electronic module ET 200SP, F-DQ 4x24VDC/2A PM HF, 15 mm width, up to PL e (ISO 13849), up to SIL 3 (IEC 61508) |
| General information / Tên kiểu sản phẩm | F-DQ 4x 24 V DC/2 A PM HF |
| General information / Firmware version / FW update possible | Yes |
| General information / usable BaseUnits | BU type A0 |
| General information / Color code for module-specific color-coded label | CC01 |
| General information / Product function / I&M data | Yes; I&M0 to I&M3 |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | V20 with HSP 470 |
| General information / Engineering with / STEP 7 configurable/integrated from version | as 6ES7136-6DB00-0CA0 |
| General information / Engineering with / PROFINET from GSD version/GSD revision | GSDML V2.45 |
| CiR - Configuration in RUN / Reparameterization possible in RUN | No |
| Supply voltage / Rated value (DC) | 24 V |
| Supply voltage / permissible range, lower limit (DC) | 19.2 V |
| Supply voltage / permissible range, upper limit (DC) | 28.8 V |
| Supply voltage / Reverse polarity protection | Yes |
| Supply voltage / power supply according to NEC Class 2 required | No |
| Input current / Current consumption (rated value) | 30 mA; without load |
| Input current / Current consumption, max. | 100 mA; without load |
| Output voltage / Rated value (DC) | 24 V |
| Power / Power consumption from the backplane bus | 70 mW |
| Power loss / Power loss, typ. | 3 W |
| Address area / Address space per module / Inputs | 6 byte; S7-300/400F CPU, 6 byte |
| Address area / Address space per module / Outputs | 6 byte; S7-300/400F CPU, 4 byte |
| Hardware configuration / Automatic encoding | Yes |
| Hardware configuration / Electronic coding element type F | Yes |
| Digital outputs / Type of digital output | Transistor |
| Digital outputs / Số ngõ ra số | 4 |
| Digital outputs / Digital outputs, parameterizable | Yes |
| Digital outputs / output type acc. to IEC 61131, type 2 | Yes |
| Digital outputs / Short-circuit protection | Yes |
| Digital outputs / Response threshold, typ. | > 3.3 A; 8 mA; 3 A |
| Digital outputs / Open-circuit detection | Yes |
| Digital outputs / Overload protection | Yes |
| Digital outputs / Limitation of inductive shutdown voltage to | sourcing output: -39 V DC in relation to 2M, sinking output: +47 V DC in relation to 2M |
| Digital outputs / Controlling a digital input | Yes; digital output, according to IEC 61131-2, type 2 |
| Digital outputs / Switching capacity of the outputs / with resistive load, max. | 2 A |
| Digital outputs / Switching capacity of the outputs / with inductive load, max. | 2 A |
| Digital outputs / Switching capacity of the outputs / on lamp load, max. | 10 W |
| Digital outputs / Load resistance range / lower limit | 12 Ω |
| Digital outputs / Load resistance range / upper limit | 2 000 Ω |
| Digital outputs / Output voltage / for signal "1", min. | 24 V; L+ (-0.5 V) |
| Digital outputs / Output current / for signal "1" rated value | 2 A |
| Digital outputs / Output current / for signal "0" residual current, max. | 0.5 mA |
| Digital outputs / Switching frequency / with resistive load, max. | 30 Hz; Symmetrical |
| Digital outputs / Switching frequency / with inductive load, max. | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| Digital outputs / Switching frequency / with capacitive load, max. | 30 Hz; observe chapter "Switching of capacitive loads" in the manual |
| Digital outputs / Switching frequency / on lamp load, max. | 10 Hz; Symmetrical |
| Digital outputs / Total current of the outputs / Current per channel, max. | 2 A; note derating data in the manual |
| Digital outputs / Total current of the outputs / Current per module, max. | 6 A; note derating data in the manual |
| Digital outputs / Cable length / shielded, max. | 1 000 m |
| Digital outputs / Cable length / unshielded, max. | 500 m |
| Interrupts/diagnostics/status information / Diagnostics function | Yes; See Chapter "Alarms/diagnostic messages" in the manual |
| Interrupts/diagnostics/status information / Substitute values connectable | No |
| Interrupts/diagnostics/status information / Alarms / Diagnostic alarm | Yes |
| Interrupts/diagnostics/status information / Alarms / Hardware interrupt | No |
| Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LED | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LED | Yes; red LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status display | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnostics | Yes; red LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnostics | Yes; green/red DIAG LED |
| Potential separation / Potential separation channels / between the channels | No |
| Potential separation / Potential separation channels / between the channels and backplane bus | Yes |
| Potential separation / Potential separation channels / between the channels and the power supply of the electronics | No |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| Suitable for safety functions | Yes |
| Highest safety class achievable in safety mode / Performance level according to ISO 13849-1 | PLe |
| Highest safety class achievable in safety mode / Category according to ISO 13849-1 | Cat. 4 |
| Highest safety class achievable in safety mode / SIL acc. to IEC 61508 | SIL 3 |
| Highest safety class achievable in safety mode / Probability of failure (for service life of 20 years and repair time of 100 hours) / Low demand mode: PFDavg in accordance with SIL2 | < 2.00E-04 |
| Highest safety class achievable in safety mode / Probability of failure (for service life of 20 years and repair time of 100 hours) / Low demand mode: PFDavg in accordance with SIL3 | < 2.00E-05 |
| Highest safety class achievable in safety mode / Probability of failure (for service life of 20 years and repair time of 100 hours) / High demand/continuous mode: PFH in accordance with SIL2 | < 1.00E-08 1/h |
| Highest safety class achievable in safety mode / Probability of failure (for service life of 20 years and repair time of 100 hours) / High demand/continuous mode: PFH in accordance with SIL3 | < 1.00E-09 1/h |
| Ambient conditions / Ambient temperature during operation / horizontal installation, min. | 0 °C |
| Ambient conditions / Ambient temperature during operation / horizontal installation, max. | 60 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, min. | 0 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, max. | 50 °C |
| Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max. | 4 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual |
| Dimensions / Chiều rộng | 15 mm |
| Dimensions / Chiều cao | 73 mm |
| Dimensions / Chiều sâu | 58 mm |
| Weights / Khối lượng xấp xỉ | 30 g |
Item code: 3RA2816-0EW20
Item code: 3RT2035-1NB30
Item code: 6MF2805-0AA00
Item code: 6ES7440-1CS00-0YE0
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.