Item code: 3RA2816-0EW20
- Unit
- Chưa cập nhật
Loading content…
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.

Module ngõ ra tương tự SIEMENS 6ES7532-5NB00-0AB0. General information / Tên kiểu sản phẩm: AQ 2xU/I ST; General information / HW functional status: FS01; General information / Firmware version: V1.0.0.
Item code
6ES7532-5NB00-0AB0
Unit
Chưa cập nhật
Supply status
Contact for quote
Required quantity (Chưa cập nhật)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | 6ES7532-5NB00-0AB0 |
| Tên gọi chính hãng | SIMATIC S7-1500/ET 200MP, analog output module, AQ 2xU/I ST (25 mm); 16-bit resolution; accuracy 0.3%; 2 channels in in a group; diagnostics; substitute value; safety-oriented switching off of load groups up to SIL 2 according to EN IEC 62061:2021 and category 2/PL c according to EN ISO 13849-1:2015; including U-connector, complete infeed and shielding set and push-in front connector |
| General information / Tên kiểu sản phẩm | AQ 2xU/I ST |
| General information / HW functional status | FS01 |
| General information / Firmware version | V1.0.0 |
| General information / FW update possible | Yes |
| General information / Product function / I&M data | Yes; I&M0 to I&M3 |
| General information / Product function / Isochronous mode | No |
| General information / Product function / Prioritized startup | No |
| General information / Product function / Output range scalable | No |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | V13 / V13.0.2 |
| General information / Engineering with / STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| General information / Engineering with / PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| General information / Engineering with / PROFINET from GSD version/GSD revision | V2.3 / - |
| General information / Operating mode / Oversampling | No |
| General information / Operating mode / MSO | Yes |
| CiR - Configuration in RUN / Reparameterization possible in RUN | Yes |
| CiR - Configuration in RUN / Calibration possible in RUN | Yes |
| Supply voltage / Rated value (DC) | 24 V |
| Supply voltage / permissible range, lower limit (DC) | 20.4 V |
| Supply voltage / permissible range, upper limit (DC) | 28.8 V |
| Supply voltage / Reverse polarity protection | Yes |
| Input current / Current consumption, max. | 110 mA; with 24 V DC supply |
| Power / Power consumption from the backplane bus | 0.65 W |
| Power loss / Power loss, typ. | 2.7 W |
| Analog outputs / Số ngõ ra tương tự | 2 |
| Analog outputs / Voltage output, short-circuit protection | Yes |
| Analog outputs / Voltage output, short-circuit current, max. | 24 mA |
| Current output, no-load voltage, max. | 22 V |
| Cycle time (all channels), min. | 3.2 ms; independent of number of activated channels |
| Output ranges, voltage / 0 to 10 V | Yes |
| Output ranges, voltage / 1 V to 5 V | Yes |
| Output ranges, voltage / -5 V to +5 V | No |
| Output ranges, voltage / -10 V to +10 V | Yes |
| Output ranges, current / 0 to 20 mA | Yes |
| Output ranges, current / -20 mA to +20 mA | Yes |
| Output ranges, current / 4 mA to 20 mA | Yes |
| Connection of actuators / for voltage output two-wire connection | Yes |
| Connection of actuators / for voltage output four-wire connection | Yes |
| Connection of actuators / for current output two-wire connection | Yes |
| Load impedance (in rated range of output) / with voltage outputs, min. | 1 k Ω; 0.5 kOhm at 1 to 5 V |
| Load impedance (in rated range of output) / with voltage outputs, capacitive load, max. | 1 μF |
| Load impedance (in rated range of output) / with current outputs, max. | 750 Ω |
| Load impedance (in rated range of output) / with current outputs, inductive load, max. | 10 mH |
| Cable length / shielded, max. | 800 m; for current, 200 m for voltage |
| Analog value generation for the outputs / Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max. | 16 bit |
| Analog value generation for the outputs / Integration and conversion time/resolution per channel / Conversion time (per channel) | 0.5 ms |
| Analog value generation for the outputs / Settling time / for resistive load | 1.5 ms |
| Analog value generation for the outputs / Settling time / for capacitive load | 2.5 ms |
| Analog value generation for the outputs / Settling time / for inductive load | 2.5 ms |
| Errors/accuracies / Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
| Errors/accuracies / Linearity error (relative to output range), (+/-) | 0.15 % |
| Errors/accuracies / Temperature error (relative to output range), (+/-) | 0.002 %/K |
| Errors/accuracies / Crosstalk between the outputs, max. | -100 dB |
| Errors/accuracies / Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
| Errors/accuracies / Operational error limit in overall temperature range / Voltage, relative to output range, (+/-) | 0.3 % |
| Errors/accuracies / Operational error limit in overall temperature range / Current, relative to output range, (+/-) | 0.3 % |
| Errors/accuracies / Basic error limit (operational limit at 25 °C) / Voltage, relative to output range, (+/-) | 0.2 % |
| Errors/accuracies / Basic error limit (operational limit at 25 °C) / Current, relative to output range, (+/-) | 0.2 % |
| Interrupts/diagnostics/status information / Diagnostics function | Yes |
| Interrupts/diagnostics/status information / Substitute values connectable | Yes |
| Interrupts/diagnostics/status information / Alarms / Diagnostic alarm | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Monitoring the supply voltage | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Wire break | Yes; Only for output type "current" |
| Interrupts/diagnostics/status information / Diagnoses / Short-circuit | Yes; Only for output type "voltage" |
| Interrupts/diagnostics/status information / Diagnoses / Overflow/Underflow | Yes |
| Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LED | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LED | Yes; red LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; red LED |
| Potential separation / Potential separation channels / between the channels | No |
| Potential separation / Potential separation channels / between the channels, in groups of | 2 |
| Potential separation / Potential separation channels / between the channels and backplane bus | Yes |
| Potential separation / Potential separation channels / Between the channels and load voltage L+ | Yes |
| Permissible potential difference / between S- and MANA (UCM) | 8 V DC |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Security / signed firmware update | No |
| Security / data integrity | No |
| Ambient conditions / Ambient temperature during operation / horizontal installation, min. | 0 °C |
| Ambient conditions / Ambient temperature during operation / horizontal installation, max. | 60 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, min. | 0 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, max. | 40 °C |
| Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Dimensions / Chiều rộng | 25 mm |
| Dimensions / Chiều cao | 147 mm |
| Dimensions / Chiều sâu | 129 mm |
| Weights / Khối lượng xấp xỉ | 200 g |
| Other / Note: | Supplied incl. 40-pole push-in front connectors |
Item code: 3RA2816-0EW20
Item code: 3RT2035-1NB30
Item code: 6MF2805-0AA00
Item code: 6ES7440-1CS00-0YE0
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.