Item code: 3RA2816-0EW20
- Unit
- Chưa cập nhật
Loading content…
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.

Module ngõ vào số SIEMENS 6ES7131-6BF00-0DA0. General information / Tên kiểu sản phẩm: DI 8x24 V DC HS; General information / HW functional status: from FS04; General information / Firmware version: V1.0.2.
Item code
6ES7131-6BF00-0DA0
Unit
Chưa cập nhật
Supply status
Contact for quote
Required quantity (Chưa cập nhật)
No online payment is required. TESFA will verify the item code, quantity, supply conditions and respond with a quotation using your contact details.
For MRO items, verifying the correct code matters more than selecting by image. TESFA checks the key technical points before confirming a quotation.
| Attribute | Product specification |
|---|---|
| Mã sản phẩm | 6ES7131-6BF00-0DA0 |
| Tên gọi chính hãng | SIMATIC ET 200SP, digital input module, DI 8x 24 V DC High Speed, Pack quantity: 1 unit, three alternative operating modes: DI, Oversampling, 4x counters, suitable for BU type A0, Color code CC01 |
| General information / Tên kiểu sản phẩm | DI 8x24 V DC HS |
| General information / HW functional status | from FS04 |
| General information / Firmware version | V1.0.2 |
| General information / FW update possible | Yes |
| General information / usable BaseUnits | BU type A0 |
| General information / Color code for module-specific color-coded label | CC01 |
| General information / Product function / I&M data | Yes; I&M0 to I&M3 |
| General information / Product function / Isochronous mode | Yes; 125 μs |
| General information / Product function / suitable for operation on PROFINET R1 IMs | Yes |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | V13 SP1 |
| General information / Engineering with / STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| General information / Engineering with / PCS 7 configurable/integrated from version | V10.0 |
| General information / Engineering with / PCS neo can be configured/integrated from version | V3.1.1 |
| General information / Engineering with / PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| General information / Engineering with / PROFINET from GSD version/GSD revision | GSDML V2.3 |
| General information / Operating mode / DI | Yes |
| General information / Operating mode / Counter | Yes |
| General information / Operating mode / Oversampling | Yes |
| General information / Operating mode / MSI | No |
| Supply voltage / Rated value (DC) | 24 V |
| Supply voltage / permissible range, lower limit (DC) | 19.2 V |
| Supply voltage / permissible range, upper limit (DC) | 28.8 V |
| Supply voltage / Reverse polarity protection | Yes |
| Input current / Current consumption, max. | 70 mA; without sensor supply |
| Encoder supply / 24 V encoder supply / 24 V | Yes |
| Encoder supply / 24 V encoder supply / Short-circuit protection | Yes; per module, electronic |
| Encoder supply / 24 V encoder supply / Output current, max. | 700 mA |
| Power loss, typ. | 1.5 W |
| Address area / Address space per module / Address space per module, max. | 45 byte |
| Address area / Address space per module / Inputs | 32 byte; 1 byte + 1 byte for QI information in DI mode; 32 bytes in Oversampling mode; 25 bytes in Counter mode |
| Address area / Address space per module / Outputs | 20 byte; In count mode |
| Hardware configuration / Automatic encoding | Yes |
| Hardware configuration / Mechanical coding element | Yes |
| Hardware configuration / Type of mechanical coding element | Type A |
| Hardware configuration / Selection of BaseUnit for connection variants / 1-wire connection | BU type A0 |
| Hardware configuration / Selection of BaseUnit for connection variants / 2-wire connection | BU type A0 |
| Hardware configuration / Selection of BaseUnit for connection variants / 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| Hardware configuration / Selection of BaseUnit for connection variants / 4-wire connection | BU type A0 + Potential distributor module |
| Digital inputs / Số ngõ vào số | 8 |
| Digital inputs / Sourcing/sinking input | P-reading |
| Digital inputs / Pulse extension | Yes |
| Digital inputs / Length | 2 s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s |
| Digital inputs / Digital input functions, parameterizable / Gate start/stop | Yes |
| Digital inputs / Digital input functions, parameterizable / Freely usable digital input | Yes |
| Digital inputs / Digital input functions, parameterizable / Counter | Yes |
| Digital inputs / Digital input functions, parameterizable / Number, max. | 4; 8 |
| Digital inputs / Digital input functions, parameterizable / Counting frequency, max. | 10 kHz |
| Digital inputs / Digital input functions, parameterizable / Counting width | 32 bit |
| Digital inputs / Digital input functions, parameterizable / Counting direction up/down | Yes |
| Digital inputs / Digital input functions, parameterizable / Digital input with oversampling | Yes |
| Digital inputs / Digital input functions, parameterizable / Values per cycle, max. | 32 |
| Digital inputs / Digital input functions, parameterizable / Resolution, min. | 7.8125 μs |
| Digital inputs / Input voltage / Rated value (DC) | 24 V |
| Digital inputs / Input voltage / for signal "0" | -30 to +5 V |
| Digital inputs / Input voltage / for signal "1" | +11 to +30V |
| Digital inputs / Input current / for signal "1", typ. | 6 mA |
| Input delay (for rated value of input voltage) / for standard inputs / parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| Input delay (for rated value of input voltage) / for interrupt inputs / parameterizable | Yes |
| Input delay (for rated value of input voltage) / for technological functions / parameterizable | Yes |
| Digital inputs / Cable length / shielded, max. | 50 m |
| Digital inputs / Cable length / unshielded, max. | 50 m |
| Encoder / Connectable encoders / 2-wire sensor | Yes |
| Encoder / Connectable encoders / permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Isochronous mode / Bus cycle time (TDP), min. | 125 μs |
| Isochronous mode / Jitter, max. | 5 μs |
| Interrupts/diagnostics/status information / Diagnostics function | Yes |
| Diagnostic alarm | Yes |
| Hardware interrupt | Yes |
| Diagnoses / Diagnostic information readable | Yes |
| Diagnoses / Monitoring the supply voltage | Yes |
| Diagnoses / parameterizable | Yes |
| Diagnoses / Monitoring of encoder power supply | Yes; module-wise |
| Diagnoses / Wire break | No |
| Diagnoses / Short-circuit | Yes; module-wise |
| Diagnostics indication LED / Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED / Channel status display | Yes; green LED |
| Diagnostics indication LED / for channel diagnostics | No |
| Diagnostics indication LED / for module diagnostics | Yes; green/red DIAG LED |
| Potential separation / Potential separation channels / between the channels | No |
| Potential separation / Potential separation channels / between the channels and backplane bus | Yes |
| Potential separation / Potential separation channels / between the channels and the power supply of the electronics | No |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Ambient conditions / Ambient temperature during operation / horizontal installation, min. | -30 °C; < 0 °C as of FS04 |
| Ambient conditions / Ambient temperature during operation / horizontal installation, max. | 60 °C |
| Ambient conditions / Ambient temperature during operation / vertical installation, min. | -30 °C; < 0 °C as of FS04 |
| Ambient conditions / Ambient temperature during operation / vertical installation, max. | 50 °C |
| Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Ambient conditions / Absolute humidity / dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions / Chiều rộng | 15 mm |
| Dimensions / Chiều cao | 73 mm |
| Dimensions / Chiều sâu | 58 mm |
| Weights / Khối lượng xấp xỉ | 28 g |
Item code: 3RA2816-0EW20
Item code: 3RT2035-1NB30
Item code: 6MF2805-0AA00
Item code: 6ES7440-1CS00-0YE0
Hướng dẫn đọc mã van điện từ SMC dòng SY3000, SY5000, SY7000 và SY9000 theo catalog hãng, kèm ví dụ SKU thật và checklist tránh đặt nhầm cấu hình.
Theo đường đi của khí nén để hiểu tiền điện đến từ đâu, tính thử chi phí và chuẩn bị checklist kiểm tra rò rỉ trong nhà máy.
Chọn ống khí PU/PA theo kích thước, áp suất tại nhiệt độ dùng, bán kính uốn và môi trường. Có bảng đối chiếu và checklist thay ống MRO.